Quote:
|
Originally Posted by rcarney
My current Definity G3si is on the 4th floor of one of my buildings. We have 75 to 100 folks moving in on the 1st floor which we currently have no presence whatsoever. I have plenty of real estate in the definity to add 75 to 100 users. My plan is to run copper feed from the Definity on the 4th floor to the IDF on the 1st floor for these users. I'm being questioned on what the distance limitation is for a copper feed off of the switch. Does anyone know?
Also, in another scenario, if I wanted to throw an EPN in that area via fiber-what is the fiber distance limitations?
Thanks in advance!
|
You are well within the distance limits for analog or digilal voice terminals. 3500 feet is the limit for a TN2224 2 wire DCP set. A 2500 set can be extended, within your building, 20,000 ft using a TN746B analog board.